New York State      
NYSERDA NYSERDA DG/CHP Integrated Data System
  Home   Facilities   Reports   Links   Help   Login     

Return to Facility Listing

Arrow Linen
467 Prospect Ave
Brooklyn, NY 11215
Map It
DG/CHP Developed by
Energy Concepts
General Facility Information
Name:Arrow Linen
Address:467 Prospect Ave
City:Brooklyn
State:NY
Zip Code:11215
County:Kings
Category:Commercial Laundry
Facility Website:
SIC:72 - Personal Services
NAICS:81 - Other Services (Except Public Administration)
ISO Zone: J - New York City
Electric Utility:Consolidated Edison
Gas Utility:KeySpan East
Time Zone:Eastern Time
Latitude:40.66 deg N
Longitude:73.984 deg W
Altitude:164 feet MSL
Developer Name:Energy Concepts
Developer Website:http://www.nrg-concepts.com
NYSERDA Project Number:7318
NYSERDA Project Manager:Jaime Ritchey
DG System Ownership:Facility
DG System Enclosure:Outdoor
System Application:Combined Heat and Power
Number of Power Units:2
Primary Fuel:Natural Gas
Total Installed Capacity:300 kW
Operating Hours Per Day:16
Operating Days Per Week:6
Operating Months Per Year:12
Peak Electric Demand:520 kW
Total Annual Electricity Usage:
Total Annual Gas Consumption:
Number of Heat Exchangers:2
Standalone Capability:No
Heat Supply Temperature:205 degrees F
DG System Installation Cost:
Third Party Operation:No
Third Party Maintenance:No
Maintenance Cost:0.01 $/kWh
Government Subsidies:
Chiller Efficiency:
Boiler Efficiency:
Electricity Export to Grid:No
Facility Electric Service Voltage:Secondary
Gas Commodity Purchased:Yes
Average Gas Cost:5.5 $/MMBtu
Average Fuel LHV:920
Base Electric Rate: SC 9-1 General Large - Low Tension; New York City - Nov05-Oct06
CHP Electric Rate: SC 14RA Standby - SC 9-1 Base; Low Tension; New York City - Nov05-Oct06
CHP Contract Demand:500
NYSERDA Incentive Program Information
Incentive Program: none
Unit 1
Description: Engine 1
Manufacture Date:
Installation Date: 04/01/2003
Commission Date:
Decommission Date:
Installed Capacity: 150 kW
Efficiency: 21.2 %
Thermal Output: 0.35826 MMBtu/h
Technology Group: 100-800 Reciprocating Engine (Lean Burn)
Prime Mover: Reciprocating Engine
Fuel: Natural Gas
Generator Type: Induction Generator
Prime Mover Manufacturer: CoastIntelligen
Prime Mover Model: 150-IC with ECS
Heat Recovery: Hot Water
Primary Heat Recovery Use: Domestic Hot Water
Secondary Heat Recovery Use: Boiler Feedwater Pre-heat
Emissions Control Technology: Unknown
Genset Packager:
System Installer: Energy Concepts
Component Integration: Customer Assembled
Controller: Third-party Off-the-shelf
Demonstration PON: 669
Unit 2
Description: Engine 2
Manufacture Date:
Installation Date: 04/01/2003
Commission Date:
Decommission Date:
Installed Capacity: 150 kW
Efficiency: 21.2 %
Thermal Output: 0.35826 MMBtu/h
Technology Group: 100-800 Reciprocating Engine (Lean Burn)
Prime Mover: Reciprocating Engine
Fuel: Natural Gas
Generator Type: Induction Generator
Prime Mover Manufacturer: CoastIntelligen
Prime Mover Model: 150-IC with ECS
Heat Recovery: Hot Water
Primary Heat Recovery Use: Domestic Hot Water
Secondary Heat Recovery Use: Boiler Feedwater Pre-heat
Emissions Control Technology: Unknown
Genset Packager:
System Installer: Energy Concepts
Component Integration: Customer Assembled
Controller: Third-party Custom
Demonstration PON: 669
Reports and Other Information
Facility Details
Facility Documentation
Project Websites
Related Webpages
None
Online Monitored Data Reports
Standardized Monitored Data Reports
Operational/Reliability Reports
Emissions Reports
None

Privacy Policies        |        Disclaimer        |        Contact Us
 

17 Columbia Circle, Albany, NY 12203-6399    Toll-Free: 1-866-NYSERDA or Local: 518-862-1090    Fax: 518-862-1091
New York City and Buffalo Regional Offices

© 2005 New York State Energy Research and Development Authority
New York State Energy Research and Development Authority